Actual feed rate heavily differs from setpoint
for longer than specified time.
There is no single solution:
1. Material handling fault
Check material discharge in Volumetric
mode.
2. Electrical system fault
Check feed rate controller and motor
cables.
Check feed rate controller for proper
setting (current limitation, speed range).
3. Calibration fault
Upon initial calibration, controller was set
so tight that the slightest change to
system properties can make system
operation unreliable.
Action : Repeat this part of
commissioning.
Parameter : R24